CleanPro® 2" Walkable T-Grid Ceiling System

The CleanPro 2" Walkable T-Grid Ceiling System is purpose-built for cleanroom applications requiring structural integrity, walkability, and compliance with stringent ISO standards. Designed for ISO Class 4 to 8 (Class 10 to 100,000) environments, this system supports the weight of personnel, equipment, and standard cleanroom filter modules while maintaining airtight integrity and alignment across the ceiling plane.

Ideal for mission-critical spaces in industries like Aerospace, Biotechnology, Healthcare, Pharmaceuticals, Microelectronics, and Semiconductors, CleanPro® walkable T-grid systems balances strength, flexibility, and modularity to simplify construction, maintenance, and expansion.

CleanPro Walkable T-Grid Ceiling Render

Key Benefits

  • Walkable Load Capacity: Engineered to safely support foot traffic and maintenance equipment in interstitial spaces, without compromising ceiling integrity or cleanliness.
  • High Cleanroom Compatibility: Designed for ISO Class 4 to 8 cleanroom environments; fully compatible with HEPA/ULPA filters, fan filter units (FFUs), and lighting fixtures.
  • Modular Installation Efficiency: Factory-precut and gasketed grid components allow for quick, consistent assembly with minimal field modifications, lowering labor costs and reducing installation time.
  • Precision and Strength in Every Connection: Die-cast zinc 4-way connectors and factory-extruded tee members ensure accurate alignment and a robust, walkable structure that meets or exceeds industry load requirements.

System Features

  • 2" Wide Extruded Aluminum Grid Members: Durable, corrosion-resistant aluminum main runners and cross-tees are bolted together to form a continuous gasketed ledge for critical sealing.
  • Factory Pre-Cut for Standard Layouts: Supplied for a standard layout of 24.5" x 48.5" centers, using 46.5" cross-tees and 144" main runners, compatible with standard 23⅝" x 47⅝" filters and 22.5" x 46.5" light fixture openings.
  • Zinc Die-Cast Connectors: Top-mounted, 4-way or customizable (splice, 3-way, corner) connectors attach securely to the grid's threaded bosses with ¼-20 hardware, ensuring structural stability and ease of field assembly.
  • Precision Suspension System: Suspended using ⅜"-16 threaded rods with left-hand/right-hand threaded turnbuckles and 7" bodies for fine leveling adjustments. Recommended hang spacing is nominally 48" x 48".
  • Airtight Gasket Seal: Continuous factory-installed gasket seals around each opening to prevent particulate infiltration and maintain positive plenum pressure.
  • Integrated Top Slot Functionality: The upper tee members are extruded with a ¼-20 threaded boss for secure mounting of connectors, tie-downs, or additional hardware.
  • Clean Finish and Packaging: Powder-coated white finish enhances reflectivity and corrosion resistance. Grid sections are paper-wrapped, boxed, and skid-packed for maximum protection and easy handling on site.

Structural Performance Ratings

Based on third-party testing, the MICRO-TW Grid System supports the following loads under standard spacing conditions:

L/180 L/240 L/360
Hanger Spacing 48" 48" 48"
Main Tee Spacing 48" 48" 48"
Max Point Load 380 lbs. 380 lbs. 380 lbs.
Max Uniform Load (PLF) 115* 115* 115*
Applied Load (PSF) 57.5* 57.5* 57.5*

*Loads have been reduced from maximum allowable limits to minimize casting stress. Additional capacity may be available based on your load placement. Contact us for details.
Based on Testing by: ESi - Engineering Systems Inc, ESi Matter No: 106495 09/06/2024
Testing Review by: BSE - Structural Engineers, Updated: 07/10/2025

Optional Component Weights

The MICRO-TW Grid System supports a wide variety of optional ceiling components. Each component adds to the overall load and should be considered when evaluating structural performance. The following table lists typical component weights per unit and corresponding distributed load:

Optional Component Weight Distributed Load
2' x 4' Ducted HEPA/ULPA Filter 35 lbs. 4.38 lbs./ft2
4' x 4' Ducted HEPA/ULPA Filter 57 lbs. 3.57 lbs./ft2
2' x 4' Fan Filter Unit (FFU) with Filter 110 lbs. 13.57 lbs./ft2
4' x 4' Fan Filter Unit (FFU) with Filter 176 lbs. 11.00 lbs./ft2
2' x 4' Honeycomb Blank Panel 1" THK 8 lbs. 1.00 lbs./ft2
4' x 4' Honeycomb Blank Panel 1" THK 16 lbs. 1.00 lbs./ft2
2' x 4' Vinyl Wrapped Panel ½" THK 12 lbs. 1.50 lbs./ft2

Note: These component weights should be included in load calculations for system design verification. The maximum allowable point load is 380 lbs., and maximum distributed load is 57.5 PSF under standard spacing conditions (48" x 48" hang spacing). For applications with multiple heavy components (e.g., multiple FFUs), consult a CleanPro® structural specialist for load distribution planning.

Engineered for Cleanroom Professionals

CleanPro® systems are engineered by a team with over 100 years of combined cleanroom design expertise. Our walkable T-grid solution is more than a ceiling—it's a scalable infrastructure platform that supports operational reliability and growth in high-stakes environments. Trust CleanPro® for ceiling systems that work above and beyond.

For full technical specifications and product details, download the PDF. Download PDF

Ready to Speak with a Cleanroom Expert?

Our team is on-hand to help assess your needs and provide a budget-friendly solution. Please fill out the form to have someone contact you, or call the number below.

Call us at (800) 442-4008

PAC GCLID:    
Lead Source:    
Source Website:    
Source Page:    
First Name: *    
Last Name: *    
Email: *    
Phone Number: *    
Company Name:    
Additional Details:    

©Production Automation Corporation. All Rights Reserved.